Cookie Consent by Free Privacy Policy Generator Switchmode strømforsyning - 24Vdc 4A 96W (IP65)
Udskriv produktside

Mean Well - Switchmode strømforsyning - 24Vdc 4A 96W (IP65)

Produktnr.: H55601  |  Producentvarekode: ELG-100-24A-3Y

Private customers (endusers) are referred to our dealers or to www.elextra.dk.
Log in / create account to view prices and order.

Central warehouse, Struer:
2 pcs. in stock. Delivery 1 weekday.

Sampakgebyr: Kr. 20,- ekskl. moms.
Forsendelse (GLS erhverv): Kr. 48,- ekskl. moms.
You must have a user account and be logged in to use this feature. For account creation Click here.
Click here for a quote by min. stk.

Features:

  • Constant voltage + constant current mode output
  • Metal housing design with functional ground
  • Built-in active PFC function
  • Class 2 power unit
  • No load / standby power consumption < 0.5W
  • IP65 rating for indoor or outdoor installations
  • Function options: Io and Vo adjustable through built-in potentiometer
  • Typical lifetime > 50.000 hours
  • 5 years warranty
  • for professional use only - This device must be installed by a qualified person.

Specifications:

  • Output:
    • DC voltage: 24 V
    • Constant current region : 12 V - 24 V
    • Rated current: 4 A
    • Rated power: 96 W (200 VAC to 305 VAC), 70 W (100 VAC to 180 VAC)
    • Ripple & noise (max.): 200 mVp-p
    • Voltage adj. range: 21.6 V - 26.4 V
    • Current adj. range: 2 A - 4 A
    • Voltage tolerance: ± 3.0 %
    • Line regulation: ± 0.5 %
    • Load regulation: ± 1.0 %
    • Setup, rise time : 1000 ms, 80 ms / 115 VAC, 500 ms, 100ms / 230 VAC
    • Hold-up time (typ.): 15 ms / 230 VAC, 10 ms / 115 VAC (at full load)
  • Input:
    • Voltage range: 100-305 VAC 142-431 VDC
    • Frequency range: 47 to 63 Hz
    • Power factor: PF = 0.97 / 115 VAC, PF = 0.95 / 230 VAC, PF = 0.92 / 227 VAC at full load
    • Total harmonic distortion: THD <20% (@load = 50% / 115 VAC, @load = 60% / 230 VAC; @load = 75% / 277 VAC)
    • Efficiency (typ.): 88 %
    • AC current: 1.1 A / 115 VAC, 0.6 A / 230 VAC, 0.5 A / 227 VAC
    • Inrush current (typ.): Cold start 60 A / 230 VAC
    • Max. PSUs on 16A circuit braker: 3 units (circuit braker type B) / 6 units (circuit braker type C) at 230 VAC
    • Leakage current: < 0.75 mA / 277 VAC
    • No load / standby power consumption: <0.5 W
  • Protection:
    • Overcurrent :
      • 95 to 108 %
      • Protection type: Constant current limiting, recovers automatically after fault condition is removed
    • Short-circuit: Hiccup mode, recovers automatically after fault condition is removed
    • Overvoltage:
      • 28 V - 34 V
      • Protection type: Shut down output voltage, re-power on to recover
    • Overtemperature: Shut down output voltage, re-power on to recover
  • Environment:
    • Working temperature: -40 °C to +90 °C
    • Max. case temperature: +90 °C
    • Working humidity: 20 - 95% RH non-condensing
    • Storage temperature, humidity: -40 °C - +80 °C, 10 - 95 % RH
    • Temperature coefficient: ± 0.03 % / °C (0 °C to 60 °C)
    • Vibration: 10 to 500 Hz, 5 G 12 min. / 1 cycle, period for 72 min. each along X, Y, Z axes
  • Safety & EMC:
    • Safety standards: UL8750 (type "HL"), CSA C22.2 no. 250.13-12; ENEC EN61347-1, EN61347-2-13 independent, EN62384; GB19510.14,GB19510.1; IP65 approved
    • Withstand voltage: I/P-O/P: 3.75K VAC, I/P-FG: 2.0K VAC, O/P-FG: 1.5K VAC
    • Isolation resistance: I/P-O/P, I/P-FG, O/P-FG: 100M Ohm / 500 VDC / 25 °C / 70 % RH
    • EMC emission: Compliance to EN55015, EN61000-3-2 Class C (@load =50%); EN61000-3-3; GB17625.1,GB17743
    • EMC immunity: Compliance to EN61000-4-2,3,4,5,6,8,11; EN61547, light industry level (surge immunity Line-Earth 6KV, Line-Line 4KV)
  • Others:
    • MTBF: 978.2K hrs min.; Telcordia SR-332 (Bellcore) ; 282.9Khrs min.; MIL-HDBK-217F (25 °C)
    • Dimensions: 199 x 63 x 35.5 mm (L x W x H)

Discount

Quantity
>= 1
>= 2
>= 4

Properties